Skip to content
Protection current transformers

Protection Current Transformers – Delivery Throughout Europe

Reliable plant protection: precise protection transformers in 5P10, 5P20 and 5P30 – delivered on the same day on request.

Protection current transformers for reliable plant protection

Do you need protection current transformers at short notice for industrial plants, switchgear or power generation plants in the low- or medium-voltage range?

We supply protection transformers in the protection classes 5P10, 5P20 and 5P30 – at short notice, reliably and, on request, throughout Europe.

acteno energy helps companies avoid unplanned downtime and protection gaps. Particularly at medium voltage, a defective protection current transformer can cause considerable operational and economic damage.

That is why, in urgent cases, we offer express delivery of protection current transformers on the same day – including technical advice on selecting the right protection class.

What is a protection current transformer?

Protection current transformers (protection transformers) are special current transformers developed for use in protection systems. Unlike measuring transformers, which are designed for maximum accuracy in the rated current range, protection transformers must deliver a linear and undistorted signal to the protection relay even at extreme short-circuit currents.

Only then can protection devices such as overcurrent, distance or differential protection relays trip quickly and correctly in the event of a fault.

What do the protection classes 5P10, 5P20 and 5P30 mean?

Protection classes indicate how precisely a protection current transformer operates in the event of an overload or short circuit, and up to which current value the transformer delivers an undistorted signal to the protection device.

A protection transformer must remain linear even at extremely high short-circuit currents – only then can the protection relay trip reliably and quickly.

The protection class is made up of three elements:

  • First number (e.g. 5) → maximum permissible error in percent
  • Letter P → stands for Protection (protection application)
  • Second number (e.g. 10 / 20 / 30) → accuracy limit factor (ALF), i.e. the multiple of the rated current up to which the transformer delivers a correct signal

Examples:

5P10

max. 5% error up to 10 times the rated current

5P20

max. 5% error up to 20 times the rated current

5P30

max. 5% error up to 30 times the rated current

10P10

max. 10% error up to 10 times the rated current

The higher the ALF value, the more robust the transformer is in the event of a short circuit – and the better suited it is to installations with high short-circuit power, such as generator feeders, power transformers or industrial power distribution systems.

Measuring transformers vs. protection current transformers – what is the difference?

Measuring transformers and protection current transformers perform different tasks within an electrical installation. While measuring transformers are designed for precise energy and consumption metering, protection current transformers ensure safe and fast fault detection in the event of a short circuit.

PropertyMeasuring transformerProtection current transformer
PurposeEnergy & consumption meteringProtection of installations, lines, generators
Accuracy classes0.2 / 0.5 / 15P10, 5P20, 5P30, 10P10
In the event of a short circuitMay go into saturationMust remain linear
ApplicationMeters, PQ analysisProtection relays, switchgear
PriorityAccuracy at rated currentLinearity at high currents

While measuring transformers offer maximum accuracy in the rated current range, protection current transformers must deliver an undistorted signal even at 10, 20 or 30 times the rated current. Only then can overcurrent, distance or differential protection devices trip reliably and without delay in the event of a fault.

Which protection class is suitable for which application?

The choice of the right protection class depends directly on the short-circuit power of the installation. The higher the possible fault currents, the higher the ALF value (accuracy limit factor) of the protection transformer should be.

Standard industrial plants

Low short-circuit power, low expected fault currents

→ 5P10

Medium-voltage switchgear & transformer stations

Higher short-circuit power, ALF must be higher

→ 5P20

Generator, motor or power generation plants

Very high fault currents, transformer must remain linear at extreme current peaks

→ 5P30

Cost-optimized protection applications

Lower requirements, a lower protection class is sufficient

→ 10P10 / 10P20

Simultaneous measurement and protection

Two different cores are required for measuring accuracy and the protection function

→ Transformer with measuring core (0.2S) and protection core (5P20)

A higher ALF figure means that the transformer delivers a correct signal even at very high fault currents and is therefore ideally suited to installations with high short-circuit power.

Low voltage (0.72 kV class)

For low-voltage applications, acteno offers compact protection current transformers in various designs and protection classes. Typical areas of application are motor feeders, production plants, industrial distribution boards and switchgear with limited installation depth.

Typical technical specifications:

  • Primary currents: 50 A to 5000 A
  • Secondary currents: 1 A or 5 A
  • Rated output: 1 to 25 VA
  • Protection classes: 5P5, 5P10, 5P20, 5P30, 10P10
  • Suitable for: motor feeders, LV switchgear, compact installations

Medium voltage (10 / 20 / 30 kV)

For the medium-voltage range, acteno provides high-quality protection current transformers in various designs. These transformers are designed for demanding protection applications such as overcurrent, distance or differential protection.

Available designs:

  • Bushing-type transformers
  • Window-type transformers
  • Support-type transformers
  • Combined transformers with measuring core + protection core

Typical areas of application:

  • Medium-voltage switchgear
  • Transformer stations
  • Power generation plants
  • Generator and motor feeders

Depending on the protection requirement, protection classes such as 5P20 or 5P30 are available to ensure safe and trouble-free tripping of the protection relays.

Our express advantage

We make sure that your installations remain protected even in the event of a fault and that downtime is reduced to a minimum.

Express throughout Europe

Fast availability all over Europe

Same-day delivery

On request, also on weekends and public holidays

Technical advice

Selection of the right protection class

Full service

Metering operations, installation and commissioning

We are here for you

Contact us for fast delivery of protection current transformers. We will be happy to advise you on the right protection class and, on request, deliver on the same day.

Focus area

We usually reply within one business day.